Shenzhen SORO Electronics Co., Ltd.

Shenzhen SORO Electronics Co., Ltd. Online UPS, Inverter/Solar Inverter, Solar Power System Solar Charge Controller, Telecom Power Solution, EV Charger

Manufacturer from China
Active Member
17 Years
Home / Products / Uninterrupted Power Supply /

RS232 interface 0.7 1ph in / out 110V UPS 10KVA / 8000W with bypass repair switch

Contact Now
Shenzhen SORO Electronics Co., Ltd.
City:shenzhen
Province/State:guangdong
Contact Person:MissElla
Contact Now

RS232 interface 0.7 1ph in / out 110V UPS 10KVA / 8000W with bypass repair switch

Ask Latest Price
Video Channel
Place of Origin :China
Brand Name :SOROTEC
Certification :CE,ROHS,ISO9000
MOQ :USD10000
Packaging Details :Standard Exported Cartons and Pallets
Delivery Time :Within 15-30days after receiving your 30% TT deposit
Payment Terms :30% TT in advance, the balance before shipping
Supply Ability :10000PCS/Month for Inverter and line Interactive UPS; Advance 3000PCS/Month for Online UPS
Model Number :HP9116B 6-10KVA
Rated Voltage :200/208VAC
Frequency :50/60 Hz
Voltage Range :176~279VAC(±3VAC)
Frequency Range :50HZ:(46~54HZ); 60HZ:(56HZ~64HZ)
Power Factor :0.98
Voltage Regulation :200/208X (1±2%)VAC
Frequency Regulation :50/60 Hz±0.05Hz
Power factor :0.7/0.8(Optional) Standard 0.7
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

RS232 interface 0.7 1ph in / out 110V UPS 10KVA / 8000W with bypass repair switch

Key Features:
1.Widely used to computer equipments, telecommunication systems and Industrial automatic control equipments.


2.Truly online design, different from offline, it can adjust the input voltage, filtering, when the AC break off, the UPS will provide an uninterruptible power source from the backup batteries.

3.Large blue back light LCD for detailed Real-time UPS status display.


4.Advanced online pure sine wave power supply system, with bypass repair switch, It can
provide a reliable, high quality AC power source to the precision equipments, can be used widely in different fields.


5.UPS will change to bypass mode when overloading or inverter fault, when overloading remove, UPS will turn to inverter mode automatically.


6.N+N Parallel Redundancy and Capacity expansion for 6-20K(up to three units)


Applications:
Servers, Data-center, critical network devices, Sensitive electronic equipment, Telecom…

Model

HP9116B 6-10KVA

6KT

6KT-XL

10KT

10KT-XL

Rated Power

6KVA/4800W

10KVA/8000W

Rated Voltage

200/208VAC

Frequency

50/60 Hz

Input

Voltage Range

176~279VAC(±3VAC)

Frequency Range

50HZ:(46~54HZ); 60HZ:(56HZ~64HZ)

Power Factor

0.98

Output

Voltage Regulation

200/208X (1±2%)VAC

Frequency Regulation

50/60 Hz±0.05Hz

Power factor

0.7/0.8(Optional) Standard 0.7

Voltage distortion

Linear load<3% Non-linear load<6%

Overload

Capability

110%~150% for 30s
change to bypass model,
Recover after load normal

Current Crest Ratio

3;1

Transfer time

0ms(AC mode→ Battery mode)

Battery

DC Voltage

240VDC

Recharge Time

7hrs to 90% of capacity after
full load discharge

Recharge Current

2A

4.2A

2A

4.2A

Display

LCD

Display input/output Voltage,
Frequency, Battery voltage,
Battery capacity, Loading rate.

Communication

Interface

Smart RS232, SNMP card
(optional), USB(optional)

Environment

Operation Temperature

0~40℃

Humidity

0~95% non-condensing

Storage Temperature

-25℃~55℃

Sea level elevation

<1500m

Noise Level(1m)

<55dB

Physical Characteristic

Wright(KG)

N.W.

81

35.5

84

36

G.W.

89

39.5

91

42

Dimension(D x W x H)mm

570 X260 X717

Inquiry Cart 0