Add to Cart
3 Phase Low Frequency Pure Sine Wave Online UPS Power Supply for Telecom
Key Features:
1.Use advanced 6th generation DSP and full digital control technologies to realize higher system stability.
2.Output power factor is 0.9, carrying capacity than conventional UPS with 10% above, as users reduce investment cost.
3.Advanced distributed active parallel technology can realize parallel operation of 6PCS UPS units without the need of centralized bypass cabinet.
4.6-inch extra large LCD that can display 12 language (Chinese ,English,Russian,Spanish,French and so on).
5.Extra wide input voltage and frequency range make it adapt to severe power grid environment
6.Intelligent battery management maintains battery automatically to prolong the battery life.
7.Standard input/output filter improves the system EMC performance.
8.Extra strong capability to withstand output overload and short circuit, ensuring the system stability and system safety under extreme conditions.
9.Layered independently-sealed ventilation channel and re-dundant fan, circuit boards with protective paints and a dust filter embedded make it highly efficient to dissipate heat and protect the product effectively under severe environment.
GP9335C Series Technical Specification:
Model | GP9335C | ||||||||||
Rectifier Type | 6p | 12p | 6p | 12p | 6p | 12p | 6p | 12p | 6p | 12p | |
Rated Nominal | 120KVA/108KW | 160KVA/144KVA | 200KVA/180KW | 300KVA/270KW | 400KVA/360KW | ||||||
Rated input voltage | 380/400/415VAC 3-phase 4-wire | ||||||||||
Rated frequency | 50/60HZ | ||||||||||
Input parameters | |||||||||||
Input voltage range | ±25% | ||||||||||
Input frequency range | 45Hz~65Hz | ||||||||||
Input soft start function | 0-100% 5-300settable | ||||||||||
Input power factor | >0.98(If harmonic filter is added) | ||||||||||
Input harmonic current (THDi) | ‹4.5%(If harmonic filter is added) | ||||||||||
Bypass | |||||||||||
Bypass voltage range | -20%~+15% | ||||||||||
Bypass frequency range | 50/60HZ±10% | ||||||||||
Output parameters | |||||||||||
Inverter output voltage | 380/400/415VAC 3-phase 4-wire | ||||||||||
Voltage stability | ±1%(Steady status),±3%(Transient status) | ||||||||||
Frequency | 50/60Hz | ||||||||||
Mains power synchronization window | ±5% | ||||||||||
Actually measured frequency accuracy (internal clock) | 50/60Hz±0.01Hz | ||||||||||
Output power factor | 0.9(Output 90kW per 100kVA) | ||||||||||
Transient response time | <5ms | ||||||||||
Inverter overload capability | At 0.9 power factor, 110% for 1 hour, 125% for 10 minutes and 150% for 60s | ||||||||||
3ph 1.5ln for 5seconds,1ph 2.9ln for 5seconds | |||||||||||
Short circuit current from inverter | |||||||||||
Maximum Bypass capability | 1000% for 100ms | ||||||||||
With 100% balanced load | <1° | ||||||||||
Phase shift | |||||||||||
characteristic | With 100% imbalance load | <1° | |||||||||
100% linear load | <1% | ||||||||||
Total harmonic | |||||||||||
Distortion(THDv) | 100% non-linear load | <3% | |||||||||
System efficiency (full load) | Up to 94% (inverter efficiency is up to 98%) | ||||||||||
Rectifier output parameters | |||||||||||
Charger output voltage stability | 1% | ||||||||||
DC ripple voltage | ≤1% | ||||||||||
Operating environment | |||||||||||
Operating temperature range | 0~40°C | ||||||||||
Storage temperature | -25~70°C(Without battery) | ||||||||||
Relative humidity | 0~95% No condensation | ||||||||||
Noise (1m) | 58-68dB | ||||||||||
Protection level | IP20 | ||||||||||
Standard | Safety: IEC60950-1 IEC62040-1-1 UL1778 EMC IEC62040-2 CLASS C2 EN50091-2 CLASS A Design andTest IEC62040-3 |
Applications:
Mainly used in large IDC rooms, bank/securities settlement center, communication network management center, semiconductor product lines and large automation production and its control system. According to the special needs of users was improved, and used in large sports venues, conference room, theater and highway and railway tunnels metal halide lamp lighting system.