Add to Cart
HP9335C Plus High Frequency Online UPS , Data Centre Stable power supply ups
HP9335C Plus Series UPS represents the best solution that is both cost effective and environmental friendly,It
delivers an excellent integrated autonomy, reduced footprint and optimum input and output performances,
guaranteeing reliable and flexible power.
Key Features:
Technical Parameters
MODEL | HP9335C Plus 10-30KVA | ||||||||
10K | 10K-XL | 15K | 15K-XL | 20K | 20K-XL | 30K | 30K-XL | ||
CAPACITY | 10KVA / 9KW | 15KVA / 13.5KW | 20KVA / 18KW | 30KVA / 27KW | |||||
PHASE | 3 Phase with Neutral | ||||||||
INPUT | |||||||||
Voltage Range | Low Line Loss | 110 VAC(Ph-N) ± 3 % at 50% Load ; 176 VAC(Ph-N) ± 3 % at 100% Load | |||||||
Low Line Comeback | Low Line Loss Voltage + 10V | ||||||||
High Line Loss | 300 VAC(Ph-N) ± 3 % | ||||||||
High Line Comeback | High Line Loss Voltage - 10V | ||||||||
Phase | Three phase with ground | ||||||||
Power Factor | ≥ 0.99 at 100% Load | ||||||||
OUTPUT | |||||||||
Output voltage | 208/220/230/240VAC(Ph-N) | ||||||||
AC Voltage Regulation | ± 1% | ||||||||
Frequency Range (Synchronized Range) | 46Hz ~ 54 Hz @ 50Hz system ; 56Hz ~ 64 Hz @ 60Hz system | ||||||||
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz | ||||||||
Overload | AC mode | 100%~110%: 10min ; 110%~130%: 1min ; >130% : 1sec | |||||||
Battery mode | 100%~110%: 30sec ; 110%~130%: 10sec ; >130% : 1sec | ||||||||
Current Crest Ratio | 3:1 max | ||||||||
Harmonic Distortion | ≦ 2 % @ 100% Linear Load; ≦ 5 % @ 100% Non-linear Load | ||||||||
Transfer Time | Line←→Battery | 0 ms | |||||||
Inverte←→Bypass | 0 ms (When phase lock fails, <4ms interruption occurs from inverter to bypass) | ||||||||
Line←→ECO | <10 ms | ||||||||
EFFICIENCY | |||||||||
AC mode | > 89% | > 89% | > 89% | > 90% | |||||
Battery Mode | > 86% | > 88% | > 87% | > 89% | |||||
BATTERY | |||||||||
Standard Model | Type | 12 V / 9 Ah | 12 V / 9 Ah | 12 V / 9 Ah | 12 V / 9 Ah | ||||
Numbers | 20(18-20 adjustable) | 2 x 20(18-20 adjustable) | 2 x 20(18-20 adjustable) | 3 x 20(18-20 adjustable) | |||||
Recharge Time | 9 hours recover to 90% capacity | ||||||||
Charging Current | 1.0 A ± 10% (max.) | 2.0 A ± 10% (max.) | 2.0 A ± 10% (max.) | 4.0 A ± 10% (max.) | |||||
Charging Voltage | 273 VDC ± 1% | ||||||||
Long-run Model | Type | Depending on applications | |||||||
Numbers | 18-20 | ||||||||
Charging Current | 4.0 A ± 10% (max.) | 4.0 A ± 10% (max.) | 4.0 A ± 10% (max.) | 12.0 A ± 10% (max.) | |||||
Charging Voltage | 273 VDC ± 1% | ||||||||
PHYSICAL | |||||||||
Standard Model | Dimension,DxWxH(mm) | 832 X250X894 | 832 X250X1275 | ||||||
Long-run Model | Dimension,DxWxH(mm) | 609 X250X768 | 832 X250X828 | ||||||
ENVIRONMENT | |||||||||
Operation Temperature | 0 ~ 40°C (the battery life will down when > 25°C) | ||||||||
Operation Humidity | <95 % and non-condensing | ||||||||
Operation Altitude | <1000m | ||||||||
Acoustic Noise Level | Less than 58dB @ 1 Meter | Less than 60dB @ 1 Meter | |||||||
MANAGEMENT | |||||||||
Smart RS-232 / USB | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC | ||||||||
USB | Power management from SNMP manager and web browser |