Add to Cart
High Frequency Online UPS HP9335c Plus 10-30kVA for Medical
Product snapshot
model :10-30KVA
Capacity :10KVA/9KW
Output voltage:208/220/230/240VAC
Input power factor: >0.9
Product details
1. High frequency online UPS 10-30kva
2. 3-stage extendable charging design for optimized battery performance
3. SNMP+USB+RS-232 multiple communications.
4. ECO mode operation for energy saving
5. Adjustable battery numbers
6. True double-conversion
3. Output power factor 0.9
4. Accepts dual-mains inputs
5. Compact Design, Lower Noise
6. Maintenance bypass available
7. Optional isolation transformer offers full isolation .
HP9335C Plus Series UPS represents the best solution that is both cost effective and environmental friendly,It delivers an excellent integrated autonomy, reduced footprint and optimum input and output performances,guaranteeing reliable and flexible power.
Technical Parameters
MODEL | HP9335C Plus 10KVA | ||||||||
10K | 10K-XL | ||||||||
CAPACITY | 10KVA / 9KW | ||||||||
PHASE | 3 Phase with Neutral | ||||||||
INPUT | |||||||||
Voltage Range | Low Line Loss | 110 VAC(Ph-N) ± 3 % at 50% Load ; 176 VAC(Ph-N) ± 3 % at 100% Load | |||||||
Low Line Comeback | Low Line Loss Voltage + 10V | ||||||||
High Line Loss | 300 VAC(Ph-N) ± 3 % | ||||||||
High Line Comeback | High Line Loss Voltage - 10V | ||||||||
Phase | Three phase with ground | ||||||||
Power Factor | ≥ 0.99 at 100% Load | ||||||||
OUTPUT | |||||||||
Output voltage | 208/220/230/240VAC(Ph-N) | ||||||||
AC Voltage Regulation | ± 1% | ||||||||
Frequency Range (Synchronized Range) | 46Hz ~ 54 Hz @ 50Hz system ; 56Hz ~ 64 Hz @ 60Hz system | ||||||||
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz | ||||||||
Overload | AC mode | 100%~110%: 10min ; 110%~130%: 1min ; >130% : 1sec | |||||||
Battery mode | 100%~110%: 30sec ; 110%~130%: 10sec ; >130% : 1sec | ||||||||
Current Crest Ratio | 3:1 max | ||||||||
Harmonic Distortion | ≦ 2 % @ 100% Linear Load; ≦ 5 % @ 100% Non-linear Load | ||||||||
Transfer Time | Line←→Battery | 0 ms | |||||||
Inverte←→Bypass | 0 ms (When phase lock fails, <4ms interruption occurs from inverter to bypass) | ||||||||
Line←→ECO | <10 ms | ||||||||
EFFICIENCY | |||||||||
AC mode | > 89% | > 89% | > 89% | > 90% | |||||
Battery Mode | > 86% | > 88% | > 87% | > 89% | |||||
BATTERY | |||||||||
Standard Model | Type | 12 V / 9 Ah | 12 V / 9 Ah | 12 V / 9 Ah | 12 V / 9 Ah | ||||
Numbers | 20(18-20 adjustable) | 2 x 20(18-20 adjustable) | 2 x 20(18-20 adjustable) | 3 x 20(18-20 adjustable) | |||||
Recharge Time | 9 hours recover to 90% capacity | ||||||||
Charging Current | 1.0 A ± 10% (max.) | 2.0 A ± 10% (max.) | 2.0 A ± 10% (max.) | 4.0 A ± 10% (max.) | |||||
Charging Voltage | 273 VDC ± 1% | ||||||||
Long-run Model | Type | Depending on applications | |||||||
Numbers | 18-20 | ||||||||
Charging Current | 4.0 A ± 10% (max.) | 4.0 A ± 10% (max.) | 4.0 A ± 10% (max.) | 12.0 A ± 10% (max.) | |||||
Charging Voltage | 273 VDC ± 1% | ||||||||
PHYSICAL | |||||||||
Standard Model | Dimension,DxWxH(mm) | 832 X250X894 | 832 X250X1275 | ||||||
Long-run Model | Dimension,DxWxH(mm) | 609 X250X768 | 832 X250X828 | ||||||
ENVIRONMENT | |||||||||
Operation Temperature | 0 ~ 40°C (the battery life will down when > 25°C) | ||||||||
Operation Humidity | <95 % and non-condensing | ||||||||
Operation Altitude | <1000m | ||||||||
Acoustic Noise Level | Less than 58dB @ 1 Meter | Less than 60dB @ 1 Meter | |||||||
MANAGEMENT | |||||||||
Smart RS-232 / USB | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC | ||||||||
USB | Power management from SNMP manager and web browser |